Angle Valve Flanged End

PN16 & PN40 Flanged End

Angle Valve Flanged End

HVAC (heating, ventilation, and air conditioning) systems use an Angle Valve Flanged End PN16 end for 2-position or modulating control of steam, hot water, or chilled water-glycol solutions up to 50% concentration. Pressure Nominale is referred to as PN. The PN prefixes the pressure rating of the flanges. For instance, the PN16 flange can function at up to 16 levels.

Standard Material:

Part. No. Material Code
Body Cast Steel GSC-25N
Stem Stainless Steel AISI 410
Disc Stainless Steel AISI 410
Seat Stainless Steel AISI 410
Size Nom. Pressure Hydraulic Inspection Body
DN PN Body Seat
15 to 175 40 60 40
200 To 300 25 37.5 25
Size L1 D C No. h t H D2 Kg
15 90 95 65 4 14 16 130 100 5.6
20 95 105 75 4 14 18 135 110 7.6
25 100 115 85 4 14 18 160 125 7.9
32 105 140 100 4 18 18 170 125 8.5
40 115 150 110 4 18 18 200 150 13.4
50 125 165 125 4 18 20 225 150 14.4
65 145 185 145 8 18 22 260 200 24
80 155 200 160 8 18 24 280 200 29
100 175 235 190 8 22 24 325 250 44
125 200 270 220 8 25 26 355 250 59
150 225 300 250 8 25 28 385 300 85
175 250 350 295 12 30 32 470 420 123
200 275 375 320 12 30 34 500 420 148
250 325 450 385 12 33 38 580 500 188
300 375 515 450 16 33 42 630 575 328